Fault Tracing - Honeywell SmartDrive Compact Guide Rapide

Couple constant et variable convertisseur de fréquence pour moteurs asynchrones
Masquer les pouces Voir aussi pour SmartDrive Compact:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

17

6. FAULT TRACING

F1 02
Fault code
Fault name
1
Overcurrent
2
Overvoltage
3
Earth fault
8
System fault
9
Undervoltage
11
Output phase supervision
13
Inverter under temperature
14
Inverter over temperature
15
Motor stalled
16
Motor overtemperature
17
Motor Underload
22
EEPROM checksum fault
Table 1: Fault codes. See User Manual for detailed fault descriptions
Fault Tracing
Fault code (02 = overvoltage)
Fault ordinal number (F1 = latest fault)
Quick corrective actions
- Check loading.
- Check cables.
- Check motor size.
Increase deceleration time (P4.3).
- Check motor Cables- Check motor.
Reset the fault and restart.
Should the fault recur, contact the technical
support.
In case of temporary supply voltage break,
reset the fault and restart.
Check supply voltage.
Check motor cable and motor.
Check that the product is operated in specified
conditions.
- Check that the cooling air is not
blocked.
- Check the ambient temperature.
- Make sure that the switching frequency is not
too high in relation to ambient temperature
and motor load (P1.16).
- Check motor.
- Check that the pump or fan is not
blocked.
- Check that motor parameters are cor
rect (P1.1-P1.5).
- Decrease motor load.
FAN: check that belt is not broken.
PUMP: check that pump is not dry.
Reset the fault and restart.
Should the fault recur, contact the technical
support.
Honeywell
6-EN

Publicité

Table des Matières
loading

Table des Matières