6. Commissioning, operation
WARNING!
Neither repairs nor structural modifications are permitted, and any would void
the guarantee.
EN
6.1.1 Tightening torque for the M12 mating connector or the M12 adapter
Select a tightening torque of 0.6 Nm.
6.1.2 Tightening torque for union nut
Select a tightening torque of 15 Nm.

6.2 Electrical connection

The electrical connection is made via an M12 x 1, 4-pin circular connector.
Output signal Pt100
Load diagram
The permissible load depends on the loop supply voltage. For communication with the
instrument with programming unit PU-448, a max. load of 350 Ω is admissible.
1083
833
583
16
0
10
Voltage U
in V
B
Output signal 4 ... 20 mA
Pin
Signal
1
L+
2
VQ
3
L-
4
C
24
30
36
WIKA operating instructions model TR21
Description
10 ... 30 V
not connected
0 V
not connected