Operating faults

FAULTS
The burner locks out during operation.
POSSIBLE CAUSES
Valve lets too little gas through.
The valve is faulty.
Earth probe.
Disappearance of the flame.
31
GB
SOLUTION
Check mains pressure and/or adjust the
valve as indicated in this manual.
Replace.
Check right position and, if necessary,
adjust as indicated herein.
Clean or replace the ionisation probe.
Check gas mains pressure and/or adjust
the valve as indicated in this manual.