ITT PumpSmart PS200 Guide De Configuration Et D'utilisation page 174

Table des Matières

Publicité

A
Free Space Required for Ventilation
NO DIRECT SUNLIGHT
3300 ft (1000 M)
104 °F (40 °C)
MAX
5
F (-15°C)
o
MIN
B
5-95% RELATIVE
HUMIDITY
NO CONDENSATION
NO CORROSIVE GASES
Refer to Hardware
Manual Technical
Data for
!
application
guidelines outside
of the above listed
limits
cable connection box
IP21~NEMA1
IP55~NEMA 12
12" [305]
Cooling Air Flow
Side View
Mains Cable
Minimum Distance
8 Inches
[200 mm]
PS200 INSTALLATION QUICK REFERENCE – WALL MOUNT UNITS
7.9"
W
[200]
TYP
Mounting
template
cut from
shipping
package
H
2.0"
[51]
TYP
NEMA1(IP21)
Free
Drill Pattern
1
Space Requirements
(All Enclosures)
A
B
H
W
Frame
Inches
Inches
Inches
Inches
Size
[mm]
[mm]
[mm]
[mm]
10.5
34.5
14.17
4.92
R2
[266]
[876]
[360]
[125]
10.8
36.4
16.06
4.92
R3
[274]
[925]
[408]
[125]
13.5
39.2
18.70
8.39
R4
[343]
[996]
[475]
[213]
14.5
43.6
23.15
9.37
R5
[368]
[1107]
[588]
[238]
15.8
47.5
26.57
10.35
R6
[401]
[1207]
[675]
[263]
1. For NEMA 12 (IP55) Free Space Requirement is 2" (50)
Around Drive Perimeter
Control/Power Wiring Layout
Minimum Distance
12 Inches
[300 mm]
!
Motor Cable
Minimum Distance
Keep control wiring
20 Inches
perpendicular to
[500 mm]
power wiring
Control Wiring
ACS800-ITTU1 NEMA 1 / NEMA 12
ACS800-ITT01 IP21 / IP55
Review the entire hardware manual prior to installation.
Failure to follow these instructions may result in serious
personal injury,death and/or equipment damage
The information provided on this sheet is for installation
reference only. Please refer to the ACS800 Installation
Manual for additional installation details
Mains /Power Wiring
PE
U1 V1 W1
U2 V2 W2
T2
T1
T3
Motor
3
Metallic Conduit
or Shielded
Cable
Power
Supply
General Notes:
1. 360
Grounded terminations are required
o
2. Ultra-rapid fuses are required to protect drive.
3. Fuse operating time is to be less than 0.5 sec.
4. Refer to Technical Data section for details
Cable Entry
NEMA 1/ NEMA 12
U1/V1/W1-U2/V2/W2
Earthing PE
R +,R-Terminals
Terminals
Frame
Max. Wire
Max. Wire
Tightening
Max. Wire
Tightening
Max. Wire
Size
Size
Dia.
NEMA 1
Torque
Size
Torque
Size
AWG
inches
Lbf-ft
AWG
Lbf-ft
mm
R2
6*
0.8
0.09-1.1
8
1.1
To 16*
R3
6*
0.8
0.09-1.1
8
1.1
To 16*
R4
4
1.14
1.5-3.0
5
2.2
To 25
R5
10...2/0
1.39
11.1
10...2/0
11.1
6...70
3/0...350
R6
2.09
14.8..29.5
4/0
5.9
95...185**
MCM**
2
2
* 6 AWG (16 mm
) rigid solid cable, 8 AWG (10 mm
) flexible stranded cable
2
** With cable lugs 6..2/0 AWG (16...70 mm
) tightening torque 14.8..29.5 Lbf-Ft (20...40 Nm.) Cable lugs are not included
Basic Dimensions
Basic Drive Dimensions
NEMA 1 / IP21
Height
1
Width
Depth
Weight
Frame Size
Inches
Inches
Inches
Lbm
[mm]
[mm]
[mm]
[kg]
15.96
6.50
8.90
20
R2
[405]
[165]
[226]
[9]
18.54
6.81
10.43
31
R3
[471]
[173]
[265]
[14]
23.87
9.45
10.79
57
R4
[607]
[240]
[274]
[26]
29.09
10.43
11.26
75
R5
[739]
[265]
[286]
[34]
34.65
11.81
15.75
148
R6
[880]
[300]
[399]
[67]
1. Includes cable conn. box
Installation Checklist
MECHANICAL
1. Check that the ambient operating conditions are suitable [Technical Data].
2. Check that drive enclosure is suitable for installation location. Install in a non-hazardous location only.
3. Check that the unit is mounted properly on a vertical non-flammable wall [Mechanical Installation]
4. Check that cooling air flows freely
5. Check the applicability of the motor and the driven equipment [Electrical Installation]
ELECTRICAL
6. If the PS200 is connected to an ungrounded power system or a high resistance grounded power system (over 30
Ohms), check that the EMC filter capacitors are disconnected.
7. The capacitors are reformed if stored over 1 year.
8. Check that the drive is grounded properly
9. Check that the input voltage matches the drive nominal input voltage
10. Check that the input power connections at U1, V1, and W1 are OK
11. Check that the appropriate line fuses are installed
12. Check that motor connections at U2, V2, and W2 are okay
13. Check the motor cable routing
14. Check that there are no power factor compensation capacitors connected between the drive and the motor.
15. Review and check that control connections inside the drive are properly wired [See control wiring diagrams].
16. Check that there are no tools or foreign objects left inside the drive.
17. With bypass connection, check that input line voltage cannot be applied to the output of the PumpSmart PS200.
18. Drive, motor connection box and other covers are in place.
Drawing is not to scale
Drawn: AI 091003
Rev2 Updated format
Dimensions in inches
Rev3 Add 01 Frame
[mm]
Checked: Tony Stavale
IP21 / IP55
U1/V1/W1-U2/V2/W2
Earthing PE
R +,R-Terminals
Terminals
Max. Wire
Max. Wire
Tightening
Max. Wire
Tightening
Dia. IP21
Dia. IP55
Torque
Size
Torque
mm
mm
Nm
mm
Nm
2
2
21
14-20
1.2-1.5
10
1.5
14-20
21
1.2-1.5
10
1.5
29
23-25
2-4
16
3
35
23-25
15
6...70
15
53
30-45
20-40
95
8
Basic Drive Dimensions
NEMA 12 / IP55
Height
Width
Depth
Weight
Inches
Inches
Inches
Lbm
[mm]
[mm]
[mm]
[kg]
20.8
10.35
9.49
35
[528]
[263]
[241]
[16]
20.8
10.35
10.74
41
[528]
[263]
[273]
[18]
30.49
14.84
10.94
73
[774]
[377]
[278]
[33]
30.49
14.84
12.14
112
[775]
[377]
[308]
[51]
36.34
16.54
16.54
170
[923]
[420]
[420]
[77]
Issue
REV
B04933A
SHEET 1 OF 1
3
-