Start / Stop Options - Single External Control Locations
2 Wire Start /Stop
X22
START / STOP
Terminal Block
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
!! NOTE !!
8
24 VDC
DIIL Must be closed for the drive to
operate. If your application does not
9
GND 1
require an E-Stop/Drive Permissive, DIIL
E-Stop
10
GND 2
may be bypassed by jumping DIIL to
X22 connections #7 or #8
11
DI IL
Note: Set parameter 12.01 to 2 Wire DI1
Start / Stop Options - Dual External Control Locations
Example: Localized Pump Start when H-O-A switch in HAND Mode
This configuration enables the user to toggle between two different control
locations. An example of this would be if the customer has one Start /Stop switch in
the field (by the pump) and the another in the control room. Using digital input 3 the
user can toggle between the two control locations.
X22
OFF
AUTO
HAND
Terminal Block
1
DI1
2
DI2
LOCALIZED / REMOTE SELECTOR
3
DI3
SWITCH
DI3 OPEN = LOCAL
DI3 CLOSED = REMOTE
4
DI4
5
DI5
REMOTE
6
DI6
START / STOP
!! NOTE !!
7
24 VDC
8
24 VDC
DIIL Must be closed for the drive to
operate. If your application does not
9
GND 1
require an E-Stop/Drive Permissive, DIIL
E-Stop
may be bypassed by jumping DIIL to X22
10
GND 2
connections #7 or #8
11
DI IL
Note:
Set parameter 12.01 to 2W DI 1- 2WDI5
PS200 – DIGITAL INPUT WIRING
2 Wire H-O-A
X22
Terminal Block
AUTO
1
DI1
OFF
2
DI2
HAND
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
!! NOTE !!
8
24 VDC
DIIL Must be closed for the drive to
operate. If your application does not
9
GND 1
require an E-Stop/Drive Permissive, DIIL
E-Stop
10
GND 2
may be bypassed by jumping DIIL to
X22 connections #7 or #8
11
DI IL
Note: Set parameter 12.01 to HOA DI1,2
Note: Set parameter 12.01 to 3W DI1P, D12P
Example : Speed Override when H-O-A switch in Hand Mode
This configuration enables the user to toggle between two different control
locations. An example of this would be if the customer has a Hand-Off-Auto
switch in the field (by the pump) and requires that in hand mode the pump be
run from the local station and in Auto mode the pump be controlled by a remote
location
AUTO
START/STOP
from Control Room
!! NOTE !!
DIIL Must be closed for the drive to
operate. If your application does not
require an E-Stop/Drive Permissive, DIIL
may be bypassed by jumping DIIL to X22
connections #7 or #8
Note:
Set parameter 12.01 to HOA DI1,2-D15
Set parameter12.11 to H-O-A
3 Wire Start /Stop
Option 1: Motor Thermistor Relay
X22
START
Terminal Block
Thermistor
1
DI1
Relay
2
DI2
3
DI3
STOP
4
DI4
5
DI5
6
DI6
T
Motor
7
24 VDC
Motor
8
24 VDC
9
GND 1
E-Stop
10
GND 2
11
DI IL
Alternate
Location
At DI3
X22
Terminal Block
OFF
1
DI1
HAND
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
8
24 VDC
9
GND 1
E-Stop
E-Stop
Note:
10
GND 2
Set Parameter 12.11 to either DI5, DI5 (INV), DI3 or DI3 (INV)
11
DI IL
Inverse setting activates speed override when switch is open
Optional Thermistor For Motor Protection
X22
Terminal Block
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
8
24 VDC
T
9
GND 1
Motor
10
GND 2
11
DI IL
Note: Set Parameter 25.06 to
Thermistor
!
WARNING
According to IEC664, the connection of the motor thermistor to a digital input requires double or
reinforced insulation between motor live parts and the thermistor. Reinforced insulation entails a
clearance and creeping distance of 8 mm (0.31 in ) for 400/500 VAC input voltages. If the thermistor
assembly does not fulfill the requirements, the other I/O terminals of the drive must be protected
against contact, or a thermistor relay must be used to isolate the thermistor from the digital input.
Failure to follow these instructions may result in serious personal injury and/or equipment damage.
Speed Override Option
Digital Specific Gravity Selection ( SG Select )
X22
Toggles between minimum
and maximum SG values
Terminal Block
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
8
24 VDC
9
GND 1
10
GND 2
11
DI IL
Note:
Set Parameter 29.12 to DI
Option 2: Motor Thermistor
X22
Terminal Block
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
24 VDC
8
24 VDC
10nf
9
GND 1
10
GND 2
11
DI IL
X22
Terminal Block
1
DI1
2
DI2
3
DI3
4
DI4
Open =SG Min.
5
DI5
6
DI6
Closed = SG Max.
7
24 VDC
8
24 VDC
9
GND 1
10
GND 2
11
DI IL
PS200 Basic Wiring PS200 v5
Copyright 2003 ITT Industries
Issue
REV
B05436A
SHEET 2 OF 2
1
-
Drawn: AI 0-02-06
Drawing is not to scale
Dimensions in inches [mm]
Checked: AES 6-23-06