Type 2030, 2031, 2031 K, 2032,
2033, 2037
8.
insTallaTiOn
8.1.
safety instructions
Danger!
risk of injury from high pressure in the equipment!
•
Before loosening the lines and valves, turn off the pressure and vent the lines.
risk of injury due to electrical shock!
•
Before reaching into the device or the equipment
reactivation!
•
Observe applicable accident prevention and safety regulations for electrical equipment!
Warning!
risk of injury from improper installation!
•
Installation may be carried out by authorized technicians only and with the appropriate tools!
risk of injury from unintentional activation of the system and an uncontrolled restart!
•
Secure system from unintentional activation.
•
Following assembly, ensure a controlled restart.
8.2.
Before installation
•
Before connecting the valve, ensure the pipelines are flush.
•
The flow direction is optional.
8.2.1.
installation position 2/2-way valve
•
The piston-controlled diaphragm valve can be installed in any installation position, preferably with the actuator
face up.
installation for self-drainage of the housing
It is the responsibility of the installer and operator to ensure self-drainage.
To ensure self-drainage:
→
Install housing inclined by angle
drainage of the housing).
→
Observe an inclination angle of 3° – 5°. Forged and cast housings feature a mark which must face upwards
(12 o'clock position).
→
The bore (in the actuator base) for monitoring leaks must be at the lowest point.
Installation
α = 10° bis 40° to the horizontal (see Figure 11:Installation position for self-
, switch off the power supply and secure to prevent
english
19