Electrical installation
Connection of system bus (CAN)
Between CAN_LOW and CAN-HIGH the CAN bus has to be terminated by resistors (120 Ω).
The Sub-D plug with an integrated terminating resistor (order no. EWZ0046, not included
in the scope of supply) complies with the recommendation DS 102-1 of CiA.
L
O F
O N
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898-2:
CAN cable in accordance with ISO 11898-2
Cable type
Impedance
Cable resistance/cross-section
Signal propagation delay
Observe the information on the bus cable length(49)!
48
O F
F
O N
E W
Z 0
0 4
6
F
F
O F
O N
Cable length
Cable length 301 ... 1000 m
On
Off
120
IN
OUT
Paired with shielding
120
(95 ... 140
300 m
70 m
/m / 0.25 ... 0.34 mm
40 m
/m / 0.5 mm
5 ns/m
On
120
IN
IN
)
2
(AWG22)
2
(AWG20)