10. Specifications
Specifications
Vacuum tightness
EN
Output signal
Output signal
Load
Voltage supply
Power supply
Accuracy specifications
Non-linearity (per IEC 61298-2)
Non-repeatability
Accuracy at reference conditions
Adjustability of zero point and span
20
Yes
see product label
4 ... 20 mA (2-wire)
20 ... 4 mA (2-wire)
0 ... 20 mA (3-wire)
DC 0 ... 10 V (3-wire)
DC 0 ... 5 V (3-wire)
DC 1 ... 5 V (3-wire)
DC 0.5 ... 4.5 V ratiometric (3-wire)
see product label
The power supply for the pressure transmitter must be made via an energy-limited electri-
cal circuit in accordance with section 9.3 of UL/EN/IEC 61010-1, or an LPS per UL/EN/IEC
60950-1, or class 2 in accordance with UL1310/UL1585 (NEC or CEC). The voltage supply
must be suitable for operation above 2,000 m should the pressure transmitter be used at this
altitude.
≤ ±0.2 % of span BFSL
≤ ±0.1 % of span
see product label
±5 %
WIKA operating instructions pressure transmitter, model S-10
≤ (power supply - 10 V) / 0.02 A
≤ (power supply - 3 V) / 0.02 A
> max. output signal / 1 mA