CHAPTER 8
FAULT CAUSES
Control set KWL 45 STS-UP/HS
8.0
Fault causes
Error/fault
Causes
KWL EC 45 does not
– Mains power supply failure 230 V
start
– Control voltage failure 12 V DC
or
– Operating mode Supply air active
impeller does not turn
(no longer turns)
– Plug not connected to KWL EC 45 or
cable break
– Ventilation stage 0 activated
– Impeller blocked
– Motor defective
– Controller defective
Vibrations
– Contamination of impellers
– Bearing damage
Abnormal noises
– Grinding impeller
– Bearing damage
– Mechanical damage
KWL EC 45 no longer
– G3 - Filter and/or protection guard
supplies the capacity
contaminated
– Design-inner panel is closed
– Ventilation stage not selected
– Bearing damage
– Heat accumulator contaminated
Troubleshooting
Check mains power supply
Check connections according to wiring diagram
Replace switching power supply SNU / SNH
Change operating mode
(target function no fault)
Check plug and control line for cable break if
necessary
Change operating stage
Note external contact
Clear blockade, clean if necessary
Contact Helios customer services
Contact Helios customer services
Check connections according to wiring diagram
Contact Helios customer services
Clean
Replace fan
Contact Helios customer services
Clean impeller, replace fan if necessary
Contact Helios customer services
Replace fan
Contact Helios customer services
Replace defective components
Contact Helios customer services
Check G3 -filter and protection guard for contami-
nation and replace G3 - filter or clean protection
guard
Open design–inner panel
Increase ventilation stage
Replace fan
Contact Helios customer services
Clean (see page 10)