Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
Heat exchanger
is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there are any
Fan
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
Drain pan
water is polluted.
▼ Maintenance List
Part
Unit
Heat exchanger
Indoor / outdoor
Fan motor
Indoor / outdoor
Filter
Indoor
Fan
Indoor
Air intake / discharge
Indoor / outdoor
grilles
Drain pan
Indoor
Ornamental panel,
Indoor
louvres
Exterior
Outdoor
99-EN
Inspection method
Check (visual / auditory)
Maintenance
Wash the heat exchanger when it is
Dust / dirt clogging, scratches
clogged.
Take appropriate measures when
Sound
abnormal sound is generated.
• Wash the filter with water when it is
Dust / dirt, breakage
contaminated.
• Replace it when it is damaged.
• Vibration, balance
• Replace the fan when vibration or
balance is terrible.
• Dust / dirt, appearance
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Dust / dirt clogging, drain
Clean the drain pan and check the
contamination
downward slope for smooth drainage.
Wash them when they are contaminated
Dust / dirt, scratches
or apply repair coating.
• Rust, peeling of insulator
Apply repair coating.
• Peeling / lift of coat
12
Troubleshooting
Confirmation and check
When an error occurred in the air conditioner, an error
code and indoor UNIT No. appear on the display part
of the remote controller.
The error code is only displayed during the operation.
If the display disappears, operate the air conditioner
according to the following "Confirmation of error log" for
confirmation.
Error code
Indoor UNIT No. in
which an error occurred
– 50 –
Confirmation of error log
When an error occurred on the air conditioner, the error
log can be confirmed with the following procedure.
(The error log is stored in memory up to 4 errors.)
The log can be confirmed from both operating status
and stop status.
2
3
1
1
When
and
buttons are pushed simultaneously
for 4 seconds or more, the following display appears.
If
is displayed, the mode enters in the error log
mode.
• [01: Order of error log] is displayed in CODE No..
• [Error code] is displayed in CHECK.
• [Indoor unit address in which an error occurred] is
displayed in Unit No..
2
Every pushing of
button used to set
temperature, the error log stored in memory is
displayed in order.
The numbers in CODE No. indicate CODE No. [01]
(latest) → [04] (oldest).
REQUIREMENT
Do not push
button because all the error log of the indoor
unit will be deleted.
3
After confirmation, push
button to return to the
usual display.