The enable zone is different if damping elements which deviate from the
standard target plate in terms of material, form and size are used�
Enable zone for selected materials*:
Material
FE360 (= mild steel)
Stainless steel
AIMg3G22
CuZn37
Copper
* Typical values for damping with a reference target of 24 x 24 x 1 mm and non-flush
installation to IEC 60947-5-2 at an ambient temperature of 20 °C�
Depending on the characteristics of the damping element there may be no
close zone�

6 Installation

The unit is non-flush mountable according to IEC 60947-5-2, type I2A18SP2�
► Ensure the unit cannot work loose (tightening torque ≤ 25 Nm).
► Adhere to the installation conditions in accordance with the figures 1 to 3:
1
16 mm
24 mm
18 mm
► Tighten the socket according to the manufacturer's indications� Observe the
socket tightening torque 0�6���1�5 Nm�
Flush installation of the fail-safe sensor is not permitted since this can result
in an increase of the sensing range up to enabling of the outputs (OSSDs)�
Enable zone
1���8 mm
0���5�6 mm
0���3�2 mm
0���3�2 mm
0���2�4 mm
2
64 mm
3
36 mm
UK
7