4.4.1 Connecting the PV generator
↻ Time required for DC connection: 15 min
↻ PV generator checked for a ground fault.
↻ DC cable with 2 x 1 or 2 x 2 strands already on the device.
↻ DC polarity checked before connection made to device.
1 Activate the connection power at the switchbox or string combiner with the DC
isolator switch.
2 For improved accessibility: Unfasten the DC input plate using the 4 screws [
T_30].
3 Unfasten the cable fitting for the DC connection [
4 Remove the sealing plug in the cable fitting used.
5 Remove the outer cladding of the DC cables and insert them through the cable
fitting.
6 Strip the insulation from DC cables according to M10 ring cable lug so that the
strand and insulation can be pressed into the cable lug shaft.
CAUTION! Risk of fire due to chemical corrosion. Cable lugs must be suitable
for the conductor material and copper busbars being used .
WARNING! Risk of short circuit due to incorrect size of the cable lug! Observe
the dimensions for the selection. [See figure 6] [} Page 188]
7 Press ring cable lug onto DC wires. When crimping, ensure that the ring cable
lug is rotated in accordance with the final installation position.
CAUTION! Use a shrink tubing (>= 6 kV/mm dielectric strength) as the clear-
ance is insufficient. This prevents a surge in voltage.
8 Guide the shrink tubing over the uninsulated crimping point and a maximum of
+0/-2
20
mm over the cable insulation and shrink-fit using manual shrink-fitting
equipment.
9 Secure the input plate using the 4 screws [
ð DC cable configured. Continue with the connection to the DC filter or
DC switch.
Connecting the DC cable to the DC filter
↻ DC cables equipped with a ring cable lug [max width 1,65 inch ]
1 Place the cable lug of cores DC- and DC+ on the busbar in accordance with the
labeling and secure it with a nut, screw and lock washer (fastening elements in
scope of supply)
2 Check that the connected cables are fitted securely.
3 Tighten the cable fittings [
» The device is connected to the PV generator.
Page 188
W_46]
53.10 In-Ibs ]
T_30 /
[
W_17 /
65 In-Ibs ].
W_46 /
Photovoltaic feed-in inverter - KACO blueplanet 87.0 - 165TL3
1
4
3
Fig. 5: Removing the DC input
plate
1
Housing base – DC side
2
Screws for mounting
3
Input plate
4
Cable fitting
Ø 11 mm
3
Fig. 6: Configuring the DC cable
1
Cable lug
2
Shrink tubing*
3
DC cable
max. 42 mm
265.50 In-Ibs
3
1
Fig. 7: DC connection with 2 DC+/-
inputs
1
DC- busbar
2
DC+ busbar
3
Cable lug (optional with 2
DC+/- inputs)
2
max.
1.65
inch
2
1
2