Operation; Mode Selection; Temperature Setting; Automatic Operation - Mitsubishi Electric Mr.SLIM PKA-A KA7 Série Manuel D'utilisation

Masquer les pouces Voir aussi pour Mr.SLIM PKA-A KA7 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Operation

About the operation method, refer to the operation manual that comes with each remote controller.
3.1. Turning ON/OFF
[ON]
Press the [ON/OFF] button.
The ON/OFF lamp will light up in
green, and the operation will start.
Note:
Even if you press the ON/OFF button immediately after shutting down the operation is progress, the air conditioner will not start for about 3 minutes.
This is to prevent the internal components from being damaged.
Settable preset temperature range
Operation mode
Cool/Dry
Heat
Auto
Fan/Ventilation

3.2. Mode Selection

Press the [F1] button to go through the op-
Fri
eration modes in the order of "Cool", "Dry",
"Fan", "Auto", and "Heat". Select the desired
Room
83ºF
Cool
Set temp.
Auto
operation mode.
83
ºF
Mode
Temp.
Fan
F1
F2
F3
F4
• Operation modes that are not available
to the connected outdoor unit models will
not appear on the display.
What the blinking mode icon means
The mode icon will blink when other indoor units in the same refrigerant
system (connected to the same outdoor unit) are already operated in a
different mode. In this case, the rest of the unit in the same group can
only be operated in the same mode.

Automatic operation

According to a set temperature, cooling operation starts if the room
temperature is too hot and heating operation starts if the room
temperature is too cold.
During automatic operation, if the room temperature changes and
remains 2.0 °C, 4 °F or more above the set temperature for 15
minutes, the air conditioner switches to cool mode. In the same way,
if the room temperature remains 2.0 °C, 4 °F or more below the set
temperature for 15 minutes, the air conditioner switches to heat mode.
Cool mode
15 minutes (switches
from heating to cooling)
15 minutes (switches
from cooling to heating)
Because the room temperature is automatically adjusted in order to
maintain a fixed effective temperature, cooling operation is performed
a few degrees warmer and heating operation is performed a few
degrees cooler than the set room temperature once the temperature is
reached (automatic energy-saving operation).
Preset temperature range
67 ~ 87 ºF (19 ~ 30 ºC)
63 ~ 83 ºF (17 ~ 28 ºC)
67 ~ 83 ºF (19 ~ 28 ºC)
Not settable
Cool
Dry
Auto
Heat
Set temperature +2.0°C, +4 °F
Set temperature
Set temperature -2.0°C, -4 °F
[OFF]

3.3. Temperature setting

<Cool, Dry, Heat, and Auto>
Room
83ºF
Cool
Set temp.
83
Fan
ºF
Mode
Temp.
F1
F2
F3
Press the [F2] button to decrease the preset temperature, and press the
[F3] button to increase.
• Refer to the table on this page for the settable temperature range for
different operation modes.
• Preset temperature range cannot be set for Fan/Ventilation operation.
• Preset temperature will be displayed either in Centigrade in 0.5- or
1-degree increments, or in Fahrenheit, depending on the indoor unit
model and the display mode setting on the remote controller.
<For IR wireless remote controller>
To decrease the room temperature:
button 3 to set the desired temperature.
Press
The selected temperature is displayed.
To increase the room temperature:
button 3 to set the desired temperature.
Press
The selected temperature is displayed.
Press the [ON/OFF] button again.
The ON/OFF lamp will come off,
and the operation will stop.
Fri
Room
84ºF
Auto
Cool
Set temp.
84
ºF
Fan
Mode
Temp.
Example display
(Centigrade in 0.5-degree increments)
F4
Fri
Auto
Fan
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr. slim pca-a ka7 série

Table des Matières