Ecoflam MAX 1 Mode D'emploi page 10

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
420010269300 Max 1
EN
NOZZLE
gph
spry
0.40
60°S
0.50
60°S
0.55
60°S
0.60
60°S
0.65
60°S
0.75
60°S
0.85
60°S
SUNTEC
AS 47 A
3
6
P
SUNTEC
SUNTEC
1
- That check valve is suitably designed for the duty.
The pump pressure is set at a value of 12 bar during the testing of burners. Before starting the burner, bleed the air
in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming.
Start the burner and check the pump feeding pressure. In case the pump priming does not take place during the
first prepurging, with a consequent, subsequent lock-out of the burner, rearm the burner's lock-out to restart, by
pushing the button on the control box. If, after a successful pump priming, the burner locks-out after the prepur-
1
1
ADJUSTMENT DATA
PUMP
OUTPUT
bar
kg/h
12
1,6
12
2
12
2,3
12
2,4
12
2,7
12
3,1
12
3,5
NOZZLE : DANFOSS H÷S 80°÷60°; DELAVAN W 60°; STEINEN S 60°
PRIMING AND ADJUSTMENT OF OIL PUMP
DANFOSS
BFP 21 R3
7
4
5
5
V
P
-
2
1
2
3
FIRING HEAD SETTING AIR DAMPER ADJUSTMENT
Pos.
0
0,3
0,5
1
1,5
2
2,5
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6
6 - TO NOZZLE
7 - CARTRIDGE FILTER
P
3
VERIFY:
+
4
V
- That piping system is perfectly sealed.
- That the use of hoses is avoided whenever is
possible (use copper pipes preferably).
- That depression is not greater than 0,45 bar, to
2
1
avoid pump's cavitation.
ging, due to a fuel pressure drop in the pump, rearm the
1 - HOSE
2 - OIL FILTER
3 - OIL COCK
Note: before starting the burner, check that the return
pipe is open. An eventual obstruction could damage the
2
3
1
10
Pos.
1,8
2,3
3
3,5
4,5
5,3
6,5
burner's lock-out to restart the bur-
ner. Do never allow the pump
working without oil for more than
three minutes.
pump sealing device.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Max 1 r

Table des Matières