Configuration

Please note
The cover is connected to the internal PC boards via the
operating voltage cable. It cannot therefore be removed
completely.
Caution
The components of the valve terminal contain elements
which are liable to damage by electrostatic charges.
The components can also be destroyed if the contact
surfaces of plug connectors are touched, or if the re
gulations for handling electrostatically vulnerable com
ponents are not observed.
Please observe the following when configuring:
1. Switch off the operating voltage.
2. Open node (screws are liable to be lost).
3. Set fieldbus address.
4. Set fieldbus baud rate.
5. Set fieldbus protocol.
6. Check compatibility with DeviceNet (as from field bus
node FB11 V2.0 of 26.02.99 or higher, see Electronics
Manual, order number 163 956 as from version
9902d).
7. Close node.
8. If the valve terminal to be connected is at the end of a
fieldbus line, a terminating resistor must be installed.
12
Festo VIFB11−..− 0208e English