Configuration

CAUTION:
The valve terminal contains components that are vulnerable
to electrostatic interference. Touching the contact surfaces
of the plug connectors and non-compliance with the hand-
ling regulations for electrostatically vulnerable components
can damage the valve terminal.
Implement configuration as follows:
1. Switch off the operating voltage.
2. Remove switch cover.
3. Use the switches to set:
- Field bus baud rate
- Node address.
4. Replace switch cover.
5. If the CPV terminal is the first or last slave in the DeviceNet,
a terminating resistor must be installed.
12