A. 0 - 10V BMS WITH WATER TEMPERATURE MONITORING
A.1.  FACTORY SETTINGS
The device is controlled via home automation. The unit starts as soon as there is a 0-10V control
signal and the set water temperature has been reached.
The unit starts as soon as the water temperature is >
28°C and the control signal is 0-10V.
Only with configuration code FCC.BR722 / FCC.BR724!
The unit starts as soon as the water temperature is < 24°C
and the control signal is 0-10V.
Activator speed in function of the incoming control
signal.
Window contact
The window contact is not activated by default and has to be activated /deactiva-
ON
ted manually .
1
2
3
4
5
6
7
8
Switch on : turn on the DIP switch 1
JAGA NV | BRIZA 22 - JFCC | MANUEL | 23.08.2021 | V.07
RS485 A/B
I2C
PC / RF
CO2
CONTROL PANEL
THERMOSTATE 1
ON
1
2
3
4
5
6
7
8
GND 0-10V 24V
GND
24V
DIPSWITCH
JAGA
GND
24V
GND
NTC1
GND
0-10V +24V
+24V
RC
GND
IN/OUT
[I]
GND
0-10 V
4-pipe
[B]
4-pipe
2-pipe
[C]
[C]
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
Tsens 1
Tsens 2
Tsens 3
Tsens 4
N L
GND
0-10V
V.H.
GND
0-10V
V.C.
N L
[A]
(200-240V
- 50Hz)
Max
Min
0
1
curve : Speed versus 0-10V control signal
ON
1
EN
BMS (V)
10
43

Publicité