B.  0-10V WITH WATER TEMPERATURE MONITORING
Configuration code : DPC.BR72
0-10 V
24 V
B.1.  FACTORY SETTINGS
The device is controlled via BMS. The unit starts when there is a 0-10V control signal and the preset
water temperature has been reached.
The unit starts if the water temperature is > 28°C/82 ̊ F and the control signal is 0-10V.
The unit starts if the water temperature is < 18 ̊ C /64 ̊ F and the control signal is 0-10V.
...
Fan speed in function of the incoming control signal.
Max
Min
0
1
40
1
+
GND
BMS (V)
10
JAGA NV | BRIZA 12 - JDPC.002 | MANUEL | 05.07.2021 | V.08
[7]
4P
curve : Speed versus 0-10V control signal
2P