C.  AUTO-CHANGE-OVER
Only in combination with a suitable heat
pump and control valve for heating and
cooling !
2⁰C
The device automatically enters cooling mode when the water temperature is 4°C/7°F below the
room temperature. If the differential between room and water temperature is less than 2°C/4°F, the
device will automatically switch to standby.
The device automatically enters heating mode when the water temperature is 4°C/7°F above the
room temperature. If the differential between room and water temperature is less than 1°C/2°F
higher than the room temperature, the device will automatically switch to standby.
Configuration code : DPC.BRC3 / DPC.BRC4 / DPC.BRC6
ONLY DPC.BRC4 /
MODE
DPC.BRC6
C.1.  FACTORY SETTINGS
C.1.1.  Without control panel
The unit automatically enters the desired operating mode ( or standby) based on the water and room
temperature. ( ,
of standby).
Auto-change-over. The unit starts when the water temperature > 28 ̊ C .
Auto-change-over. The unit starts when the water temperature < 18 ̊ C .
The unit is in standby.
1 Speed . The unit runs at the preset speed.
JAGA NV | BRIZA 12 - JDPC.002 | MANUEL | 05.07.2021 | V.08
1⁰C
Standby mode
1
24 V
+
GND
- DPC.BRC3
1⁰C
[C]
4P
2P
4⁰C
EN
41