Remote Controller Wiring
Indoor unit
Remote Controller wiring
(field supply)
Terminal for Remote Controller wiring
Remote Controller cable shall be (2 x min 0.3 mm²), of double
insulation PVC-sheathed or rubber sheathed cable. Total cable
length shall be 50 m or less.
Be careful not to connect cables to other terminals of Indoor Unit
(e.g. power source wiring terminal). Malfunction may occur.
Do not bundle together with the power source wiring or store in the
same metal tube. Operation error may occur.
Remove The Remote Controller From Indoor Unit
1. Remove the top case from the bottom case.
2. Remove the wiring between Remote controller and Indoor Unit
terminal. Remove the bottom case from the Control board cover
by loosening the screws. (3 pieces)
Claw
(2 places)
Disconnect the
Remote controller
wiring
8
Remote Controller
No polarity
Insert the
driver and
slightly turn.
Flat-blade
screwdriver
Bottom
case
Mounting The Remote Controller
For exposed type
Preparation: Make 2 holes for screws using a driver.
Mount the top case.
Align the claws of the top
case and then align the claws
of the bottom case.
1
2
Cut here with
a nipper and
remove the burr
with a file.
Claw (2 places)
Connect the remote control
wiring
Arrange the wires along the groove
of the case.
Bottom case
For embedded type
Preparation: Make 2 holes for screws using a driver.
Mount the top case.
Align the claws of the top
case and then align the claws
of the bottom case.
Avoid the wire
being caught.
Claw (2 places)
Connect the remote
control wiring
Mount the bottom case to
the wall.
U P
Wall to which
the remote
controller is
fixed
Hole for screw
Claw (2 places)
Screw
(field supply)
Clamper
(field supply)
Pass through
the hole
Remote controller terminal board
Remove the coating. Approx. 6 mm
Top case
(Back side)
(Back side)
Remove the sheath. Approx. 180 mm.
Make sure the wiring connection is in the
correct direction.
Mount the bottom case
to the wall.
Pass the wire through the hole
in the centre of the bottom case.
U P
Hole for
screw
Claw (2 places)
Screw
(field supply)
Remote controller
terminal board
Remove the coating.
Top case
(Back side)
Bottom case
(Back side)
Make sure the wiring
connection is in the correct
direction.
Approx. 6 mm

Publicité

loading

Ce manuel est également adapté pour:

Wh-sqc12h9e8Wh-sqc16h9e8