For model WH-SQC09H3E8
Terminal on the outdoor unit
Colour of wires (Connecting cables)
Terminal on the indoor unit
(Power Supply Cord)
Terminals on the isolating device
from power supply (Disconnecting
means)
For model WH-SQC12H9E8, WH-SQC16H9E8
Terminal on the outdoor unit
Colour of wires (Connecting cables)
Terminal on the indoor unit
(Power Supply Cord)
Terminals on the isolating device
from power supply (Disconnecting
means)
RCCB
RCCB/
ELCB
*1
*1
Holder
(Clamper)
Power Supply Cord
Power Supply Cord
WIRE STRIPPING AND CONNECTING REQUIREMENT
Wire stripping
Indoor/outdoor
connecting
terminal board
5mm or
more
No loose strand
(gap between
when insert
wires)
7
INSTALLATION OF REMOTE CONTROLLER AS
ROOM THERMOSTAT
Remote Controller 3 mounted to the Indoor Unit can be moved to the room and serve as Room Thermostat.
Installation Location
Install at the height of 1 to 1.5 m from the floor (Location where average room temperature can be detected).
Install vertically against the wall.
Avoid the following locations for installation.
1. By the window, etc. exposed to direct sunlight or direct air.
2. In the shadow or backside of objects deviated from the room airflow.
3. Location where condensation occurs (The Remote Controller is not moisture proof or drip proof.)
4. Location near heat source.
5. Uneven surface.
Keep distance of 1 m or more from the TV, radio and PC. (Cause of fuzzy image or noise)
Main Power Supply
or Main + Backup
Booster Heater
Heater Power Supply
Power Supply
L
L
L
N
L
N
A1
A2
A3
L
L
L
N
L
N
A1
A2
A3
Power Supply 1
Power Supply 2
Booster + Backup
Main Power Supply
Heater Power Supply
L
L
L
N
L
L
A1
A2
A3
B1
B2
L
L
L
N
L
L
A1
A2
A3
B1
B2
Power Supply 1
Power Supply 2
Holder
(Clamper)
Connecting Cable
Conductor
fully insert
ACCEPT
1
2
3
4
5
1
2
3
4
5
Indoor unit/Outdoor unit
connection
1
2
3
4
5
L
N
1
2
3
4
5
B3
Indoor unit/Outdoor unit
L
N
B3
connection
Terminal
Terminal screw
Board
M4
M5
*1
*1 - Earth wire must be longer than other cables for safety reasons
Conductor
Conductor not
over insert
fully insert
PROHIBITED
PROHIBITED
Tightening torque cN•m {kgf•cm}
157~196 {16~20}
196~245 {20~25}
7