Install the indoor unit
1. Engage the slots on the indoor unit to the hooks of installation
plate 1 . Ensure the hooks are properly seated on the installation
plate by moving it left and right.
2. Fix the screws 5 to the holes on the hooks of installation plate 4 ,
as illustrated below.
Slots
Indoor unit back
Water piping installation
Water inlet and water outlet in indoor unit are used for connection
to water circuit. Please request a licensed technician to install this
water circuit.
This water circuit must comply with all relevant European and
national regulations, i.e. IEC/EN 61770.
Be careful not to deform the piping to excessive force when doing
piping connection job.
Use Rp 1¼" nut for both water inlet and outlet connection and
clean all pipings with tap water before connecting to the indoor unit.
Cover the pipe end to prevent dirt and dust when inserting it
through a wall.
Choose proper sealer which can withstand the pressures and
temperatures of the system.
If an existing tank is to be connected to this indoor unit, ensure the
pipes are clean before water pipe installation is carried out.
Be sure to use two spanners to tighten the connection. Tighten the
nuts with torque wrench: 117.6N•m.
Indoor unit
If non-brass metallic piping is used for installation, make sure to
insulate the pipes to prevent galvanic corrosion.
Make sure to insulate the water circuit pipes to prevent reduction
of heating capacity.
After installation, check the water leakage condition in connection
area during test run.
Installation plate 1
Hooks
Wall
Installation plate 4
Screws 5
Note: Do not lift the
Indoor Unit by holding the
refrigerant and water pipes
to prevent damage of the
pipes.
Torque wrench
Spanner
CAUTION
Do not over tighten, over tightening cause water leakage.
Refrigerant pipe installation
1. Please make flare after inserting flare nut (located at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
2. Do not use pipe wrench to open refrigerant piping. Flare nut
may be broken and cause leakage. Use proper spanner or ring
wrench.
3. Connect the piping:
Align the center of piping and sufficiently tighten the flare nut
with fingers.
Be sure to use two spanners to tighten the connection.
Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
Spanner or
Wrench
Piping size (Torque)
Gas
ø15.88mm (5/8")
[65 N•m]
Liquid Refrigerant Pipe
CAUTION
Do not over tighten, over tightening cause water leakage.
CAUTION
Please take extra precaution when open the control board
cover 6 and control board 7 for indoor unit installation and
servicing. Failure to do so may cause injury.
Water Inlet
Water Outlet
Torque wrench
Liquid
ø9.52mm (3/8")
[42 N•m]
Gas Refrigerant Pipe
5