4 Connection
This product has been carefully manufactured and tested but there is a
risk that damage can occur from such as transportation and incorrect
handling. Therefore, the procedure below should be followed during
initial installation:
Hazardous voltage. Will cause death or serious injury. Turn off and lock
out all power supplying this device before starting work on this equip-
ment.
Mounting and electrical connection of the softstarter shall be made in
accordance with existing laws and regulations and be performed by
authorized personnel.
Before connecting the Softstarters PSE size 18...170 to operational
supply voltage for the first time, the control supply voltage must be
turned on to ensure that the by-pass relays are in the open position.
This is necessary to avoid unintentional starting of the equipment during
connection.
1.
Connect the terminals 1L1, 3L2 and 5L3 to the operational voltage on
the power supply line side.
2.
Connect the terminals 2T1, 4T2 and 6T3 to the motor.
Connecting Softstarters PSE18...PSE370 Inside Delta will cause dam-
age to the equipment, and there is a risk of death or serious injury.
PSE
In Line
Inside Delta
Softstarters Type PSE18...PSE370 User Manual short form 1SFC132369M9901 7