Table 6.1: Parameter list
Description
Rated Current of motor
Start Ramp time
Stop Ramp time
Initial/End Voltage
Current Limit
Torque Control during start ramp
Torque Control during stop ramp
Kick Start
Electronic Motor Overload
Protection (EOL)
Tripping class
Type of operation
Underload Protection
Level
Type of Operation
Locked Rotor Protection
Level
Type of Operation
FieldBus Control
Fieldbus Address
Fieldbus interface
Download Parameter
Operation When Fault
Type of Operation
Int only
Timeout
Baudrate
Modbus frame format
HAnd = Manual reset of the protection or fault.
1
Auto = Automatic reset of the protection or fault.
2
OFF = Fieldbus is not allowed to control the motor.
On = Fieldbus is allowed to control the motor.
3
255 = Address of the FieldBusPlug will be used.
dPon = Download of parameters from PLC enabled.
4
dPoF = Download of parameters from PLC blocked.
Display
9.6/19.2/38.4/57.6/76.8 kBaud
Softstarters Type PSE18...PSE370 User Manual short form 1SFC132369M9901 13
Setting range
Individual
1...30 s
OFF, 1...30 s
30...70 %
1.5...7 x I e
OFF, On
OFF, On
OFF, 30...100 %
OFF, 10A, 10, 20, 30
HAnd, Auto
1
OFF, 0.2...1 x I e
HAnd, Auto
1
OFF, 0.5...7 x I e
HAnd, Auto
1
OFF, On
2
0...255
FbP, Int
4
dPon, dPoF
trIP, LocC
5
HAnd, Auto
6
0.5 ... 60s
7
8o1, 8E1,8n2,8n1
Accessible only if On is previously selected.
5
trIP = Trip on fault.
LocC = Local control on fault - hardwire control is possible
Accessible only if trIP is previously selected.
HAnd = Manual reset of the protection or fault.
6
Auto = Automatic reset of the protection or fault.
Databits(8), Parity (Even, odd, no), Stopbits (1, 2)
7
Default
Actual
value
setting
Individual
10 s
OFF
40 %
7.0 x I e
OFF
On
OFF
10
HAnd
OFF
HAnd
OFF
HAnd
OFF
3
255
FbP
dPon
LocC
HAnd
0.5
19.2
8E1