5.3

Internal Built-in Components

Ascertaining the maximum number of conductors
Heat is generated in each terminal box. It is generated due to contact resistance at the
clamping units and due to the electrical lines installed in the enclosure.
However, the maximum permissible temperature of the terminal box must not be
exceeded! As a result, the current loads for the electrical circuits and therefore the
maximum permissible number of conductors must be observed.
5.3.1 Determine the Number of Conductors using the US EC Type Examination Certificate
The maximum permissible number of conductors can be read out of the table in the
US EC Type Examination Certificate for the type. Output data is the current load [in A]
and the conductor cross-section [in mm
To correctly use the specified number of conductors, please note:
Each inserted conductor and each internal connection conductor must be counted
individually.
Jumpers and protective conductors do not count.
Example: Enclosure 8150
Enclosure 8150/1-0176-0116-091...
Wire size AWG
Current
Amps
16
14
5
10
27
53
15
20
20
25
30
Enclosure 8150/1-0176-0176-091...
Current
Amps
16
14
5
10
32
64
15
24
20
11
25
30
35
40
45
50
60
65
70
Enclosure 8150/1-0236-0176-150...
Current
Amps
16
14
5
10
45
89
15
34
20
15
25
30
35
40
45
50
60
65
70
In the white area of the electrical capacity table, the permitted numbers of the current carrying conductors inside the enclosure are indicated
(in and out counts as two wires) depending on wire size and continuous current.
In the shaded area of the electrical capacity table, additional conductors/terminals are permitted up to space limit of the enclosure.
In the area with dark diagonal lines, no conductors are permitted.
212727 / 815060300170
2021-02-25·IO00·III·en·02
Product Selection, Project Engineering and Modification
12
10
39
19
43
22
22
22468E00
Wire size AWG
12
10
8
6
4
48
24
53
13
27
17
37
10
24
17
44
11
28
7
20
11
30
8
20
17
Wire size AWG
12
10
8
6
4
67
33
74
18
38
24
53
15
33
23
62
16
38
11
28
16
42
11
31
24
2
/AWG]
Enclosure 8150/1-0236-0176-091...
Current
Amps
16
14
5
10
34
68
15
26
20
11
25
30
35
40
45
50
60
65
70
22469E00
Enclosure 8150/1-0300-0200-150...
Current
Amps
16
14
5
10
48
95
15
36
20
16
25
30
35
40
45
50
60
65
70
22471E00
Terminal boxes
Series 8150/1, Series 8150/2
Wire size AWG
12
10
8
6
4
51
25
56
14
29
18
40
11
25
18
47
12
29
8
21
12
32
9
24
18
Wire size AWG
12
10
8
6
4
71
35
79
19
40
25
57
16
36
25
66
17
41
11
30
17
45
12
33
26
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
US
22470E00
22472E00
22015E00
15