WIRING CONNECTIONS
DIMENSIONS (IN INCHES)
GFSX1
Cover &
Sealing
Chamber
2.85
5.91
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not
guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
GFCI
SWITCH
TECHNICAL DATA
Hazardous and environmental ratings
Class I, Division 2, Groups B, C, D
Class I, Zone 2, IIA, IIB+H2
Class II, Groups E, F , G; Class III
NEMA 4X
IP66
NEMA 4
Agency certifications
NEC
UL 508, UL 1203, UL 121201
CEC
CSA C22.2 No. 14, No. 25, No. 213
Torques in.-lbs. (N‐m)
Captive cover screws
60 (6.8)
Ground screw (with
18 (2.0)
back box)
Electrical ratings
120A
125VAC
5mA trip setting
Temperature range
‐40°C to +55°C (-40°F to +131°F)
Weights* lbs. (kg.)
Single gang
5.2 (2.4)
Double gang
9.2 (4.2)
*Weights are based on aluminum EDS back box.
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2022
EX. ENRX RECEPTACLE
EDS back box
EDS aluminum back box
EDS iron back box
Wire size range
16-10 AWG (1.5 - 4.0 mm 2 )
Wire temperature limits
16 AWG
14 AWG
14 AWG
12 AWG
10 AWG
90°C rated insulation min.
Replacement parts
Flange gasket
Captive cover screw
REPLACEMENT PARTS
Eaton's Crouse-Hinds series products are designed
to provide years of reliable performance. However,
should the need for replacement parts arise, they are
available through your authorized Eaton's Crouse-
Hinds distributor, your local Eaton's Crouse-Hinds
representative or the Eaton's Crouse-Hinds Sales
Service Department, 1201 Wolf Street, Syracuse, New
York 13208, Phone 866-764-5454.
CONNECTION
15A @ 40°C (104°F)
15A @ 55°C (140°F)
20A @ 40°C (104°F)
20A @ 50°C (122°F)
20A @ 55°C (140°F)
ENRX K1
ENRX K2
Revision 1
New 11/22
IF 1937