Ambient Conditions; Electrical Specifications; Measuring With The Benning Cflex - Benning CFlex 1 Notice D'emploi

Masquer les pouces Voir aussi pour CFlex 1:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 16
5.1.6
Length of the measuring loop: approx. 46 cm
5.1.7
Cable diameter of the measuring loop: approx. 8.5 mm
5.1.8
Cable length from measuring loop to housing: approx. 1.8 m
5.1.9
Cable length (housing to the 4 mm safety plugs): approx. 0.5 m
5.1.10 Housing dimensions: (L x W x H) = 120 x 70 x 26 mm
5.1.11
Weight of the device: 325 g
6.

Ambient conditions

-
The BENNING CFlex 1 is intended for making measurements in dry environment.
-
Maximum barometric elevation for making measurements: 2000 m,
-
Overvoltage category: IEC 60664/ IEC 61010 → 600 V category III, 1000 V category II
-
Contamination class: 2 (EN 61010-1),
-
Protection class: IP 30 (DIN VDE 0470-1, IEC/ EN 60529)
IP 30 means: Protection against access to dangerous parts and protection against solid
impurities of a diameter > 2.5 mm, (3 - first index). No protection against water, (0 - second
index).
-
Operating temperature and relative humidity:
For operating temperatures from 0 °C to 50 °C: relative air humidity lower than 80 %, non-
condensing
-
Storage temperature: The BENNING CFlex 1 can be stored at temperatures between
- 10 °C and + 60 °C, at a relative air humidity lower than 70 % without batteries.
7.

Electrical specifications

Note: The measuring accuracy is specified as
-
a relative part of the final measuring range value
This specified measuring precision is valid for temperature of 23 °C ± 5 °C and for a relative
humidity lower than 80 %.
7.1 Alternating current ranges
Output voltage: 100 mV
10 mV
1 mV
Measuring range
30 A
300 A
3000 A
*
The measuring accuracy is specified for a sinusoidal curve. The stated accuracy is specified
for conductors that are centrally clamped by means of the measuring loop  (see figure 3).
For conductors that are not centrally clamped, an additional error has to be considered.
Distance from the middle
Load impedance:
Noise:
Band width (-3 dB): 10 Hz to 10 kHz
Phase error:
8.

Measuring with the BENNING CFlex 1

8.1 Preparing the measurement
Operate and store the BENNING CFlex 1 at the specified storage and operating temperatures
only! Do not permanently expose the device to sunlight.
-
Nominal voltage and nominal current of the enclosed safety measuring lead comply with the
respective values of the BENNING CFlex 1. The safety measuring lead is firmly connected
with the BENNING CFlex 1 and is not detachable.
-
Check the insulation of the safety measuring lead. If the insulation is damaged, the
BENNING CFlex 1 must be scrapped immediately.
-
Do not clamp a live conductor with by means of the measuring loop before the
BENNING CFlex 1 is connected with a multimeter.
-
Strong sources of interference in the vicinity of the BENNING CFlex 1 might involve unsta-
04/ 2019
/ A
in the 30 A measuring range
AC
AC
/ A
in the 300 A measuring range
AC
AC
/ A
in the 3000 A measuring range
AC
AC
Measured value
0 . . . 30 A
30 . . . 300 A
300 . . . 3000 mV
300 A . . . 3000 A
300 . . . 3000 mV
25 mm
50 mm
75 mm
min. 10 kΩ (input resistance of the multimeter)
0.03 A / 0.075 A / 0.5 A
< ± 1°
BENNING CFlex 1
Output
within the frequency range 45 Hz - 65 Hz
0 . . . 3000 mV
± (3.0 % of the final measuring range value)
± (3.0 % of the final measuring range value)
± (3.0 % of the final measuring range value)
± (1.0 % of the final measuring range value)
± (2.0 % of the final measuring range value)
± (3.0 % of the final measuring range value)
Measuring precision*
Positioning error
8

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cflex 2044068044069

Table des Matières