General Information; Ambient Conditions; Electrical Specifications - Benning IT 105 Notice D'emploi

Masquer les pouces Voir aussi pour IT 105:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 35
- Connect the red measuring lead/jack L 5 to the external conductor L.
- Connect the black measuring lead/jack N 7 to the neutral conductor N.
- Connect the green measuring lead/jack PE 6 to earth PE.
In case of an incorrect mains voltage, measurement will be blocked.
M Warning symbols. "Warning of electrical danger!", "Attention! Please observe documentation!" and
"Tester is overheated!"; please observe the relevant sections of this operating manual.
N Symbol indicating a defective fuse

5. General information

The BENNING IT 105 is intended for electrical safety tests in compliance with DIN VDE 0100-600
(IEC 60364-6) and DIN VDE 0105-100 (EN 50110).
-
Appliance dimensions: (length x width x height) = 235 x 132 x 92 mm
-
Appliance weight: 1370 g incl. batteries

6. Ambient conditions

-
The BENNING IT 105 is intended for making measurements in dry environment,
-
Maximum barometric elevation for making measurements: 2000 m,
-
Overvoltage category/ setting category: IEC 61010-1 → 300 V category III,
-
Contamination class: 2,
-
Protection class: IP 40 (DIN VDE 0470-1 IEC/ EN 60529)
IP 40 means: Protection against access to dangerous parts and protection against solid impurities of
a diameter > 1 mm, (4 - first index). No protection against water, (0 - second index).
-
EMC: EN 61326-1
-
Ambient temperature and relative humidity:
For ambient temperatures from 0 °C to 40 °C: non-condensing
-
Storage temperature: The BENNING IT 105 can be stored at any temperature within the range of
- 25 °C to + 65 °C (relative humidity from 0 to 90 %). The batteries should be removed from the instru-
ment for storage.

7. Electrical specifications

Note: The measuring accuracy is specified as the sum of
-
a relative fraction of the measured value and
-
a number of digits (counting steps of the least significant digit).
The specified measuring accuracy is valid for temperatures within the range of 18 °C to 28 °C and for a
relative humidity lower than 80 %.
7.1 Voltage (V) frequency (Hz)
Measuring range
0 V - 440 V AC/DC
45 Hz - 65 Hz
7.2 Continuity test (R
Measuring range
0.15 Ω - 199 Ω
Measuring current:
Open-circuit voltage:
Number of periodic testing (DIN EN 61557-4): approx. 4000
7.3 Insulating resistance measuring (R
Measuring range
0.20 MΩ - 199 MΩ
Test voltage:
250 V
Test current:
> 1 mA, < 2 mA in case of a short-circuit
Number of periodic testing (DIN EN 61557-2): approx. 3000
Test voltage indication: ± 5 %
11/ 2018
)
LOW
> 200 mA
> 4 V, < 8 V
DC
ISO
/ 500 V
/ 1000 V
DC
DC
Resolution
1 V
1 Hz
Resolution
max. 0.01 Ω
)
Resolution
max. 0.01 MΩ
, - 0 % + 20 %
DC
BENNING IT 105
Accuracy
± (5 % + 2 digits)
± 1 Hz
Accuracy
± (2 % + 5 digits)
Accuracy
± (5 % + 5 digits)
19

Publicité

Table des Matières
loading

Table des Matières