Télécharger Imprimer la page

LEGRAND Lexic 0046 80 Fiche Technique page 5

Publicité

VARIABLES
Dat a a dd re ss e s
Both variables and groups of variables can be required. All the variables with consecutive addresses
can be required at one time. The following is the table with the addresses and the meaning of the
variables.
Address
HEX
0x325
0x329
0x32d
0x331
Note 1: The only writable value is 0x0000000 in order to reset the stored value.
Different values won't have effect.
The following table must be used to retrieve all information of the real time measurements.
The user can poll on both tables without any more operation, just change the Modbus address in the
protocol data message.
Address
Description
Byte n.
0x1000
Long
Phase 1 : phase voltage
0x1002
Long
Phase 2 : phase voltage
0x1004
Long
Phase 3 : phase voltage
0x1006
Long
Phase 1 : current
0x1008
Long
Phase 2 : current
0x100a
Long
Phase 3 : current
0x100c
Long
0
0x100e
Long
Chained voltage : L1-L2
0x1010
Long
Chained voltage : L2-L3
0x1012
Long
Chained voltage : L3-L1
0x1014
Long
3-phase : active power
0x1016
Long
3-phase : reactive power
0x1018
Long
3-phase : apparent power
0x101a
WORD
3-phase : sign of active power
0x101b
WORD
3-phase : sign of reactive power
0x101c
Long
3-phase : total positive active energy
0x101e
Long
3-phase : total positive reactive energy
0x1020
Long
For future use
0x1022
Long
0
0x1024
WORD
3-phase : power factor
0x1025
WORD
3-phase : sector of power factor (cap or ind)
0x1026
WORD
Frequency
0x1027
Long
3-phase : average power
0x1029
Long
3-phase : peak maximum demand
0x102b
WORD
Time counter for average power
0x102c
Long
Phase 1 : active power
0x102e
Long
Phase 2 : active power
0x1030
Long
Phase 3 : active power
0x1032
WORD
Phase 1 : sign of active power
0x1033
WORD
Phase 2 : sign of active power
0x1034
WORD
Phase 3 : sign of active power
0x1035
Long
Phase 1 : reactive power
0x1037
Long
Phase 2 : reactive power
0x1039
Long
Phase 3 : reactive power
0x103b
WORD
Phase 1 : sign of reactive power
0x103c
WORD
Phase 2 : sign of reactive power
0x103d
WORD
Phase 3 : sign of reactive power
COMMUNICATION PROTOCOL
046 80
Read/Write
DEC
805
R
809
R
(1)
813
R/W
(1)
817
R/W
Format
Long
3-phase : Total positive active energy
Long
3-phase : Total positive reactive energy
Long
3-phase : Partial positive active energy
Long
3-phase : Partial positive reactive energy
09/11/2011
Description
Energy
Average power
Unit
mV
mV
mV
mA
mA
mA
mV
mV
mV
W/100
W/100
W/100
(2)
(2)
kWh/100
kvarh/100
1/100
(1)
Hz/10
W/100
W/100
minutes
W/100
W/100
W/100
(2)
(2)
(2)
var/100
var/100
var/100
(2)
(2)
(2)

Publicité

loading