ABB ACS880-01 Manuel D'installation page 9

Masquer les pouces Voir aussi pour ACS880-01:
Table des Matières

Publicité

Compliance with the European Machinery Directive
The drive is an electronic product which is covered by the European Low Voltage
Directive. However, the drive includes the Safe torque off function and can be
equipped with other safety functions for machinery which, as safety components, are
in the scope of the Machinery Directive. These functions of the drive comply with
European harmonized standards such as EN 61800-5-2.
Resistor braking
Drive type
Internal brake
P
brcont
kW
U
= 525...690 V
N
ACS880-01-07A3-7
***
ACS880-01-09A8-7
***
ACS880-01-14A2-7
***
ACS880-01-018A-7
***
ACS880-01-022A-7
***
ACS880-01-026A-7
***
ACS880-01-035A-7
***
ACS880-01-042A-7
***
ACS880-01-049A-7
***
ACS880-01-061A-7
55
ACS880-01-084A-7
65
ACS880-01-098A-7
90
ACS880-01-119A-7
110
ACS880-01-142A-7
132
ACS880-01-174A-7
160
ACS880-01-210A-7
200
ACS880-01-271A-7
250
*
Connected in series
***
Contact ABB for P
brcont
du/dt filters
Drive type
U
= 525...690 V
N
ACS880-01-07A3-7
ACS880-01-09A8-7
ACS880-01-14A2-7
ACS880-01-018A-7
chopper
R
Type
min
ohm
***
2×JBR-01*
***
2×JBR-01*
***
SACE15RE22
***
SACE15RE22
***
SACE15RE22
***
SACE15RE22
***
SACE15RE22
***
SACE15RE22
***
SACE15RE22
13
2×SAFUR90F575*
13
2×SAFUR90F575*
8
SAFUR90F575
8
SAFUR90F575
6
SAFUR80F500
6
SAFUR80F500
4
SAFUR125F500
4
SAFUR125F500
. and R
.
min
du/dt filter type
NOCH0016-6X
NOCH0016-6X
NOCH0016-6X
NOCH0030-6X
Update notice 5
Example brake resistor(s)
R
E
ohm
kJ
240
44
240
44
22
420
22
420
22
420
22
420
22
420
22
420
22
420
16
3600
16
3600
8
1800
8
1800
6
2400
6
2400
4
3600
4
3600
P
R
Rcont
kW
0.21
0.21
2
2
2
2
2
2
2
9
9
4.5
4.5
6
6
9
9

Publicité