LEGRAND DAKER DK Plus Manuel D'installation page 58

Masquer les pouces Voir aussi pour DAKER DK Plus:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
INDICATION
The UPS switches into
stored energy mode and
then back into normal
mode when a connected
device is turned on or the
UPS switches back and
forth between the two
modes.
Strange noise or smell
The UPS switches off after
a total discharge of the
batteries
Error code table
ERROR CODE
Er05
Er06
Er07
Er11
Er12
Er14
Er28
Er39
58
DIAGNOSTIC
-
-
-
Battery weak or faulty
Output short-circuit
UPS over-temperature
Inverter overload
Fans out of order
Bypass overload
Battery problem during the start-up process of the UPS
5 Troubleshooting
SOLUTION
A power strip could be connected to
the UPS. Do not use it.
See also if there is any damage to the
utility wall receptacle or if the cord plug
is faulty. Replace them if needed.
If the problem persists, contact the
LEGRAND Technical Support Service.
Shut down immediately the UPS.
Disconnect the mains and contact the
LEGRAND Technical Support Service.
The function of autorestart is enabled
by default. When the mains is available,
the UPS restarts in normal mode to
supply the loads.
MEANING
EPO mode

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

3 101 703 100 493 101 713 100 553 101 723 100 75

Table des Matières