Duty & Modulating Classification / Classification Fonctions & Régulation
EN15714-2 STANDARD DUTY CLASSIFICATION
ENDURANCE +
Please consult our Electric Actuator Guide for detailed information.
Pour plus d'information, merci de consulter notre Guide Servomoteur Electrique.
S4 motor duty according to IEC 60034-1 Standard / Service moteur S4 selon la norme IEC 60034-1
S4 : Intermittent duty with starting
Repetition of cycles including :
- Starting period D
- Period of constant speed N
- Rest period R
Duty rating D.R (in %) = M / (R+M) * 100
TYPE OF OPERATION
FONCTIONNEMENT
On/Off (Class A/A+)
Inching/Positioning (Class B/B+)
Modulating (Class III)
Continuous Modulating (Class II)
(1)
VAC only. Uniquement courant alternatif
Note on torque data:
- Max torque data corresponds to the starting period D
- Operating torque corresponds to the constant speed period N
Note sur les valeurs de couple :
- Le couple max correspond à la période de démarrage D
- Le couple de manoeuvre correspond à la période de régime constant N
Tel. : +33 (0)1 34 07 71 00 - Fax : +33 (0)1 34 07 71 01 - mail@bernardcontrols.com - www.bernardcontrols.com
A
B
ON-OFF
INCHING/
POSITIONING
A
B
A+
B+
BC DUTY & MODULATING CLASSIFICATION
BERNARD CONTROLS STANDARD
DUTY RATING
FACTEUR DE SERVICE
S4 - 30 %
S4 - 30 %
S4 - 50 %
S4 - 100 %
4 rue d'Arsonval - CS 70091 - 95505 Gonesse CEDEX France
C
D
MODULATING
CONTINUOUS
MODULATING
III
II
III+
II+
I
S4 : Service Intermittent à démarrage
Suite de cycles comprenant :
- Période de démarrage D
- Période de régime constant N
- Période de repos R
Facteur de service (%) = M / (R+M) * 100
MAX. STARTS / HOUR
DEMARRAGES / HEURE MAX
PERFORMANCE +
( RESOLUTION,
Dead band,
Response Time,
Linearity)
(1)
360
(1)
360
1 200
3 600
3