Two-Hand Control and E-Stop (switch 1 in position 6)

2 pairs of 2-hand buttons can be connected in this function together with
1 e-stop loop. The number of connected button pairs has to be selected
on the device.
K1 and K2 can only be activated, if 4 conditions are fulfilled:
- First all button pairs have to be in initial position.
- The e-stop contacts must be closed and manual start must be activated.
- Both buttons of 1 pair have to be pressed within 0.5 sec.
- All connected pairs have to be operated within 15 sec.
If changeover contacts are used in the 2-hand buttons the switchover time
has to be less then 50 ms. If it is longer the outputs K1 and K2 are switched
off and the unit gives failure code 7. This failure is stored and can only be
reset by disconnecting the auxiliary supply.
After e-stop or power failure the start button must always be activated.
The e-stop loop must be closed and all 2-hand button pairs must be in
initial position.
Function Diagram
Auxiliary voltage
(A1/A2)
Button 1 S1 (S11/S12)
Button 1 S2 (S13/S14)
Button 2 S1 (S21/S22)
Button 2 S2 (S23/S24)
E-stop
Start button (S43/S44)
K1/K2
(13-14, 23-24, 33-34)
48 (no button activated)
58 (all buttons activated)
: off
: on
: flashing
2-hand control and e-stop,
with 2 pairs of buttons with 2 NO contacts each and 1 e-stop loop

Set-Up Instructions

The device has to be connected as shown in the application examples.
When connecting the push-buttons in parallel or in series the safe function
of the relay is disabled. The buttons must be designed and installed in
a way, that it is not possible to manipulate or to operate them without
intention.
The distance between push buttons and dangerous area must be chosen
in a way that it is not possible to reach the dangerous area after release of
one button before the dangerous movement comes to standstill.
The safety distance "S" is calculated with the following formula:
S = V x T + C
a) moving speed of person V = 1 600 mm/s
b) stopping time of the machine T (s)
c) Additional safety distance C = 250 mm
If the risc of accessing the dangerous area is prohibited while the push
buttons are pressed e.g. by covering the buttons, C can be 0. The minimum
distance has to be in this case 100 mm. See also EN ISO 13851.
Settings on switch 10
Switch
Number of
10
button pairs
0
1
2
3
4
5
6-9
position not allowed (failure 5)
Terminal designation
Ter-
Pair of buttons with
minal
2 NO contacts each
S11
Pair 1, button S1
S12
S14
S13
Pair 1, button S2
S21
S22
Pair 2, button S1
S24
S23
Pair 2, button S2
1 E-stop loop and 1 Start button
S31
S32
M8447
S34
S33
S41
S42
S44
S43
Semiconductor outputs
Output
E-stop loop open or starting
conditions not fulfilled or failure
48
in feedback circuit or on acknow-
ledge button/start button.
58
Press acknowledge button.
44
Type of
button contacts
1
2 NO contacts
2
2 NO contacts
1
2 C/O contacts
1
2 NO contacts
2
2 NO contacts
1
2 C/O contacts
Pair of buttons with
2 C/O contacts each
button S1,
NO contact
button S1,
common connector
button S1,
common connector
button S1,
NC contact
button S2,
NC contact
button S2,
common connector
button S2,
common connector
button S2,
NO contact
E-stop, channel 1
E-stop, channel 2
not connected
Start button
Flashing signal
position. For a new start
all buttons have to be
the starting conditions.
K1, K2 are energized.
Feedback circuit for
external contactors
no
no
no
yes
yes
yes
Feedback circuit for
external contactors
Feedback circuit
Continuous signal
All buttons in initial
linked according to
All buttons are
activated,
BH 5910 / 23.06.22 en / 594A