Wiring
Before installation, make sure that power has
been switched off at the breaker and check that
the circuit is dead with a voltage tester.
The leads consist of three wires:
Black = line
White = neutral
Red
= load
If in doubt, identify the individual conductors with
a voltage tester or contact a qualifi ed electrician.
NEUTRAL
HOT
Standard wiring for the HBS 300 and HBS 200 High Bay Occupancy Sensors
www.steinel.net
(800) 852-4343
All manuals and user guides at all-guides.com
L
O
A
D
LINE (BLACK)
NEUTRAL (WHITE)
LOAD (RED)
Operation
The HBS 300 and HBS 200 operate by turning
lights ON automatically when occupancy
is detected and OFF when the space is left
vacant and the time delay has elapsed.
Light level function
The light level feature keeps lighting
OFF during daylight hours, regardless of
occupancy. A light level delay-off function
prevents the sensor from responding to
temporary changes in ambient light level. If
the ambient light level is brighter than the set
target value, the sensor will wait for one minute
before turning lights OFF. If motion is detected
within this time, lights will remain ON. After no
motion is detected for one minute and the light
level has been greater than the target value,
the lights will turn OFF and remain OFF until
the daylight level drops below the target set
point and motion is detected.
Initial power up
Upon initial power up, the load will turn ON
for up to one minute. If no motion is detected,
the load will switch OFF. If motion is detected
and the target light level setting is less than
the daylight level, the load will stay ON for the
selected time delay setting (per DIP switch
setting). If the daylight level at power up is
greater than the target light level setting, the
load will switch OFF regardless of occupancy.
Surge protection
The surge protection feature will reset the
sensor automatically after: power surges,
power outages, and power shortages. Surge
protection protects the sensor if it is miswired
as well. If miswired, shut off power, correct
the wiring, and the sensor will then operate
correctly.
Wireless Group Control
Any HBS 300 or HBS 200 sensor can have the
option of wireless group control by adding an
MF1-UL Wireless Group Control Module.
HBS sensor
MF1-UL
HBS sensor
back box
Wireless Group
housing
Controller
www.steinel.net
(800) 852-4343
7