The units envision the signalling of the
possible unit malfunctions. These si-
gnals are indicated by the fl ashing
alarm key (bell) on the left part of the
display. If the bell is pressed again, it
allows to display the alarm in progress.
The rearm of these alarms can take
place automatically or manually (on the
Message
• No water circulation on the system hydraulic side in winter
functioning mode
High pressure
• No circulation on the geothermy/well hydraulic side in
circuit 1
summer mode
• No DHW hydraulic side circulation in DHW mode
• Machine without refrigerant gas
Low pressure
• Little water circulation on the system cooling side in sum-
circuit 1
mer mode or geothermy/well side in winter or DHW mode
• No water circulation on the system hydraulic side in winter
functioning mode
High pressure
• No water circulation on the geothermy/well hydraulic side
circuit 2
in summer mode
• No DHW hydraulic side circulation in DHW mode
• Machine without refrigerant gas
Low pressure
• Little water circulation on the system cooling side in sum-
circuit 2
mer mode or geothermy/well side in winter or DHW mode
• No water circulation on the well/geothermy side in cooling
Gas anti-freeze
circuit N°1 winter or DHW mode
circuit 1
• No water circulation on the system side in cooling circuit
N°1 summer mode
• No water circulation on the well/geothermy side in cooling
Gas anti-freeze
circuit N°2 winter or DHW mode
circuit 2
• No water circulation on the system side in cooling circuit
N°2 summer mode
Temperature of the cooling-heating system water below the
System
set-point
water anti-freeze
Temperature of the DHW system water below the set-point
DHW
water anti-freeze
Temperature of the geothermy/well system water below the
Geothermy-well
set-pointt
water anti-freeze
Probe error
The probe cable is interrupted
Contact opening of the cooling-heating system side water
flow safety device installed outside the heat pump (flow
System flow meter
meter), due to lack of water circulation
Contact opening of the geothermy/well system side water
Geothermy/well
flow safety device installed outside the heat pump (flow
flow meter
meter), due to lack of water circulation

Alarms summary table

basis of the type and seriousness of the
alarm that has occurred). To reset the
alarm message, the bell key must be
pressed again (remember that resetting
the alarm does not solve the cause that
generated it, but just the display is can-
celled). The following table lists the pos-
sible errors that the unit can generate,
Alarm description
and a brief explanation of the possible
causes.
Also remember that the possibility exists
to display an alarms log, which states
the last alarms that have occurred on
the unit, ordered by date. This log can
be activated using the combination of
keys.
Cause of error
• Pompa idraulica spenta, bruciata,ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Rottura impianto frigorifero
• Filtri acqua sporchi
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Rottura impianto frigorifero
• Filtri acqua sporchi
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico
• Pompa idraulica spenta, bruciata, ecc...
• Pressione lato acqua a zero bar
• Rubinetti di intercettazione impianto chiusi
• Rottura fusibile all'interno del quadro elettrico