Maintenance
9.2 Maintenance
Installer maintenance includes cleaning the heat exchanger
and fans. Dependent on the conditions, this must done about
once every three years.
1
Switch off the appliance on the control panel (Press the
key for 5 seconds; the appliance will be switched off
through software) and switch off the power.
3
Remove the move the front cover.
All manuals and user guides at all-guides.com
> 5 sec.
6284-A
6285-A
6289-A
Renovent Excellent
4
Remove the heat exchanger. Be careful not to damage the
foam parts in the appliance.
5
Rinse the exchanger with hot water (max. 55 ºC) and a
regular detergent. Rinse the exchanger with hot water.
6
Take off the display cover.
Note!
First disconnect the connectors on the rear of the
display cover.
2 x
Chapter 9
6290-A
6291-A
6292A
25