Fault
Fault
Cause
code
Pressure sensor supply fan
E100
defective.
Red pressure hoses blocked
(non-locking
or "kinked".
fault)
Pressure sensor extract fan
E101
defective.
Blue pressure hoses blocked
(non-locking
or "kinked".
fault)
E103
Bypass fault .
(non-locking
fault)
E104
Extract fan defective.
(locking
fault)
E105
Supply fan defective.
(locking
fault)
The temperature sensor that
E106
measures the outdoor tempe-
(locking
rature is defective. .
fault)
The temperature sensor that
E107
measures the temperature of
(non-locking
the extract air is defective.
fault)
If present: The temperature
E108
sensor that measures the ex-
(non-locking
ternal temperature is defective.
fault)
E999
Dip switches on control board
(locking
not set correctly.
fault)
Note!
If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way
round.
Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round.
All manuals and user guides at all-guides.com
Action appliance
- Switches to constant rpm control.
- The preheater switches on at outdoor
temperatures below 0°C.
- Switches to constant rpm control.
- The preheater switches on at outdoor
temperatures below 0°C.
- None.
correctly connected or effective;
wiring or stepper motor).
- Both fans are switched off.
- Preheater(s) is switched off.
- If applicable: Postheater(s) is switched
off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater(s) is switched off.
- If applicable: Postheater(s) is switched
off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater(s) is switched off.
- Bypass closes and is blocked.
- Bypass closes and is blocked.
- Postheater is switched off.
- If applicable: Geo heat exchanger is
switched off.
- Appliance does nothing; red fault LED
on multiple switch is not activated
either.
Renovent Excellent
Chapter 8
Action installer
• Take the voltage from the appliance.
• Check the red pressure hoses (and
pressure tubes) for fouling, kinking
and damage.
• Take the voltage from the appliance.
• Check blue pressure hoses (and
pressure tubes) for fouling, kinking
and damage.
• Take the voltage from the appliance.
• Check connection stepper motor;
replace wiring or stepper motor.
• Take the voltage from the appliance.
• Replace extract fan.
• But voltage back on appliance; Fault
will automatically be reset.
• Check cabling.
• Take the voltage from the appliance.
• Replace.
• Put voltage back on appliance; Fault
will automatically be reset.
• Check cabling.
• Take the voltage from the appliance.
• Replace temperature sensor.
• Put voltage back on appliance; fault
will automatically be reset.
• Take the voltage from the appliance.
• Replace indoor temperature
sensor.
• Replace external temperature
sensor.
• Put dip switches incorrect position.
(see § 8.1).