Diagnostic et suppression des défauts
82
Numéro de
Texte court
diagnostic
382
Sensor communication
Diagnostic de la configuration
400
AIO simulation output
401
DIO simulation output
403
Calibration AIO
404
Calibration AIP
405
COMM timeout DIO 1...8
406
IOM offline
407
COMM timeout AIO 1...2
408
Invalid range AIO 1...2
409
RTD temp out of range 1...2
410
Data transfer
411
Hart device 1...15 has
malfunction
412
Processing download
413
NMT 1...15: element is open
or short
415
Hart device 1...15 offline
434
Real time clock defective
436
Date/Time incorrect
437
Configuration incompatible
438
Dataset
441
AIO 1...2 current output
alarm
442
AIO 1...2 current output
warning
443
AIO 1...2 Input not HART
compatible
Mesures correctives
1. Check connection of sensor
electronics
2. Restart device
3. Replace sensor electronics
Deactivate simulation AIO
output
Deactivate simulation DIO
output
1. Restart device
2. Change I/O module
1. Restart device
2. Change I/O module
1. Check wiring
2. Change I/O module
1. Check wiring
2. Change I/O module
1. Check wiring
2. Change I/O module
1. Check device configuration.
2. Check wiring.
1. Check electronic modules
2. Change I/O or main
electronic module
1. Check connection
2. Retry data transfer
1. Check wiring
2. Change I/O module
Download active, please wait
1. Check NMT wiring
connection
2. Replace NMT
1. Check wiring
2. Change I/O module
Replace main electronics
Check date and time settings.
1. Restart device
2. Contact service
1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
1. Check process
2. Check current output
settings
1. Check process
2. Check current output
settings
AIO select compatible HART
input.
Micropilot NMR84
Signal
Comportement du
d'état
diagnostic
[au
[au départ usine]
départ
usine]
F
Alarm
C
Warning
C
Warning
F
Alarm
F
Alarm
F
Alarm
F
Alarm
F
Alarm
C
Warning
C
Warning
F
Alarm
F
Alarm
C
Warning
C
Warning
C
Warning
C
Warning
M
Warning
F
Alarm
M
Warning
F
Alarm
C
Warning
C
Warning
Endress+Hauser