α
2 Simple Application Controllers
13.4.6
Fine Offset Adjust
The fine adjust should only be performed after both Gain and Offset Adjusts have
been performed.
1) From the TopMenu, select "Others..."
2) From the Others... menu, select "Analog In"
3) From the Analog In menu select an input that is configured for TC input.
4) Select "Offset fine" from the Analog Input settings menu.
5) Using the + and - buttons, enter a value from -31°C to 31°C (-55.8°F to 55.8°F).
Press the OK button when finished.
AL2-2TC-ADP 13
T o p M e n u
C l o c k S e t
L A N G U A G E
O t h e r s . . .
O t h e r s . . .
S e r i a l
Com
L i g h t
T i me
A n a l o g
I n
A n a l o g
I n
I 0 1
I 0 2 : PT 1 0 0
I 0 3 : TC
I 0 3
M o d e
C a l i b r a t e
O f f s e t
f i n e
I 0 3
O f f s e t
f i n e
0 ° C
ENG-82