TERMINAL ENCLOSURE (D2LBS/D2LCS/D2LDS)
Refer to the General Installation instructions before proceeding.
Note: Terminal cover is removable to assist in the installation process.
To avoid the risk of water ingress, when removing the gland plates, do not
damage or compromise the gasket. Contact Crouse-Hinds for replacement
gland plates if damaged.
1.
Remove gland plates and drill desired conduit entries in accordance with
the spacing chart for Myers hubs (Chart 2) and the gland plate dimensional
drawing (Figure 3).
Drill conduit entries in "designated area" found in the gland plate dimensional
drawing (Figure 3). Be sure to consider wiring and bending when planning
entries.
IF 1316 • 12/19
CAUTION
NOTE
Copyright © 2019, Eaton's Crouse-Hinds Division
CHART 2
FIGURE 3 - GLAND PLATE DIMENSIONAL DRAWING
4.93
TOP
6.20
(125.2)
(157.5)
DESIGNATED AREA
4.93
6.20
SIDES
(125.2)
(157.5)
ENTRIES IN THIS AREA MAY INTERFERE
WITH INTERNAL COMPONENTS.
2.
Install appropriate Myers hubs per desired entries selected.
3.
Reinstall gland plate to stainless steel terminal housing and be sure to
tighten screws to the torque values provided in the torque requirement
chart (Chart 1).
inches (millimeters)
17.41 (442.2)
16.14 (410.0)
12.81 (325.4)
6.50 (165.1)
DESIGNATED AREA
1.70 (43.2)
Ø 1.50 (38.1)
BREATHER
1.57
(39.9)
Page 3