SKD32..
SKD82..
SKD60
SKD62..
For more information, see Technical data [➙ 19]
Ordering (example)
Type / Stock number
SKD62/MO / S55195-A129
ASC1.6
Specify stock number if available.
1)
Siemens
Smart Infrastructure
ASC9.3
Double auxiliary switch
Adjustable switching points
Note: ASZ7.3
ASC1.6
Auxiliary switch
Switching point 0...5 % stroke
Designation
1)
Actuator Modbus RTU
Auxiliary switch
ASZ7.3
Potentiometer
0...1000 Ω
For the combination SIMATIC S5/S7 and use of positioning
feedback, we recommend actuators with DC 0...9.8 V
feedback signals.
The signal peaks that occur in the potentiometer ASZ7.3
may result in error messages on Siemens SIMATIC. This is
not the case when combined with Siemens HVAC
controllers. The reason is that SIMATIC has a higher
resolution and faster response time.
Use the potentiometer as voltage divider on the 3-wire
connection. Powering the potentiometer over the wiper may
shorten the life cycle of the potentiometer. Signal peaks
increase in frequency and scope over the lifespan in this
operating mode.
ASK50
Mechanical stroke inverter
0% actuator stroke
corresponds to 100% valve
stroke
Mount between valve and
actuator
Number of pieces
1
1
11
CM1N4561en
2021-02-17