Technical data

Power supply
Operating voltage
Frequency
Maximum power consumption at 50 Hz
External supply cable fuse
Function data
Positioning time at 50 Hz
Spring-return time
Positioning force
Nominal stroke
Maximum permissible medium temperature (valve fitted) -25...150 °C
Signal inputs / signal outputs
Control signal
Siemens
Smart Infrastructure
SKD32..
SKD82..
SKD6..
SKD62/MO
SKD32.21
SKD32.50
SKD32.51
SKD82.50, SKD82.50U
SKD82.51, SKD82.51U
SKD60..
SKD62..
SKD32..
SKD82..
SKD6..
1)
SKD32.21
Opening
Closing
SKD32.5..
Opening, closing
SKD82.5..
SK6..
Opening
Closing
1)
SKD32..
SKD82..
SKD62..
SKD32..
SKD82..
SKD6..
AC 230 V ± 15 %
AC 24 V ± 20 % (SELV/PELV)
50 / 60 Hz
16 VA / 12 W
11 VA / 8 W
17 VA / 12 W
9 VA / 7 W
14 VA / 10 W
10 VA / 8 W
14 VA / 10 W
Min. 0.5 A, slow
Max. 6 A slow
Min. 1 A, slow
Max. 10 A slow
30 s
10 s
120 s
30 s
15 s
8 s
15 s
1000 N
20 mm
< 0 °C:
Requires stem heater ASZ6.6
3-position
DC 0...10 V
DC 4...20 mA
0...1000 Ω
19
CM1N4561en