fisair DIPHUSAIR-MT2 Manuel D'installation Et De Maintenance page 87

Humidificateurs isothermiques par injection de vapeur sèche
Table des Matières

Publicité

Electronics
SKD60
From version ..L onward
1)
Direction of operation
ON
Reverse acting
OFF *
Direct acting
* Factory setting: all switches OFF
** Only considered when DIL switch 3 ON
(control signal = DC 4...20 mA)
SKD60
Up to and including version ..K
2)
4
Siemens
Smart Infrastructure
1)
Fail-in-place (behaviour in
case of control signal loss) **
Stops at current
position
Closes
, SKD62..
2)
1
Connection terminals
2
DIL switches
3
LED status indication
4
Stroke calibration
DIL switches
Positioning signal Y
Positioning feedback U
DC 4...20 mA
DC 0...10 V
Relationship between
positioning signal Y and
volumetric flow
1
Connection terminals
2
DIL switches
3
LED status indication
4
Stroke calibration
Flow characteristic
lin = linear
log = equal
percentage
CM1N4561en
2021-02-17