Signal inputs / signal outputs
Positioning signal Y SK6..
Override control Z SK6..
Position feedback U SK6..
Enhanced functions SKD60
Selection of direction of operation
Stroke limit control
Sequence control
Signal addition
Communication SKD62/MO
Communication protocol
20
Siemens
Smart Infrastructure
Input impedance
DC 0...10 V
DC 4...20 mA
Signal resolution
Hysteresis
Resistor
Z not connected, priority terminal Y
Z connected directly to G
Z connected directly to G0
Z connected to M via 0...1000 Ω
Load impedance
DC 0...9,8 V
DC 4...19.6 mA < 500 Ω
, SKD62UA
2)
SKD60,
Direct-acting / reverse-
SKD62UA
acting
SKD62UA
Range of lower limit
Range of upper limit
SKD62UA
Terminal Y
Starting point of
sequence
Operating range of
sequence
SKD62UA
Z connected to R of
Frost protection monitor
Frost protection monitor
Modbus RTU
Number of nodes
Adress range
Factory setting
Transmission formats
Factory setting
Baud rates (kBaud)
Factory setting
Bus termination
Factory setting
100 kΩ
240 Ω
< 1 %
1 %
1000 Ω
No function
Max. stroke 100 %
Min. stroke 0 %
Stroke proportional to R
> 10 kΩ
DC 0...10 V / DC 10...0 V
DC 4...20 mA / DC 20...4 mA
0...1000 Ω / 1000...0 Ω
0...45 % adjustable
100...55% adjustable
0...15 V adjustable
3...15 V adjustable
0...1000 Ω, added to Y signal
QAF21..
DC 1,6 V, added to Y signal
QAF61..
RS-485, not galvanically isolated
Max. 32
1...248 / 255
255
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
1-8-E-1
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Auto
120 Ω electronically switchable
Off
CM1N4561en
2021-02-17