Télécharger Imprimer la page

Lenze ECS E Serie Consignes De Sécurité page 27

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Show/Hide Bookmarks
2.3
Residual hazards
2.3.1
Residual hazards - ECSxE supply module
Protection of persons
ƒ Before working on the supply module, check that no voltage is applied to the power
ƒ The heatsink has an operating temperature of > 70 °C:
ƒ The leakage current to PE is > 3.5 mA AC or > 10 mA DC. Therefore, two PE
ƒ For operation of the supply module on an earth-leakage circuit breaker:
Protection of devices
ƒ All pluggable terminals must only be connected or disconnected when no voltage is
ƒ The power terminals +UG, -UG and PE are not protected against polarity reversal.
EDKCSXX0XX DE/EN/FR/ES/IT 4.0
terminals
– because the power terminals +UG, -UG, BR0 and BR1 carry hazardous voltages for
at least 3 minutes after mains disconnection.
– Direct skin contact with the heatsink results in burnings.
connections are installed for protective reasons.
– Comply with the requirements of EN 50178 for high leakage currents!
– The supply modules are internally equipped with a mains rectifier. In the case of a
short circuit to frame, a non-pulsating DC residual current can prevent AC
-sensitive or pulsating DC-sensitive earth-leakage circuit breakers from being
tripped and thus neutralize the protective function for the whole equipment
operated on this earth-leakage circuit breaker.
applied!
– Observe the polarity when wiring the power terminals!
Residual hazards
Residual hazards - ECSxE supply module
Safety
2
27

Publicité

loading

Ce manuel est également adapté pour:

Ecs a serieEcs k serie