INDOOR UNITS INSTALLATION
4.7 REMOVING / ASSEMBLING ELECTRICAL BOX
?
N O T E
Only RPI-(1.5~2.0)FSRE models have the possibility to change the
location of the electrical box. All other RPI models (150Pa) must maintain
the factory location for the electrical box.
The electrical box of this indoor unit allows three possible
configurations, for RPI-(1.5~2.0)FSRE. At the factory, the
electrical box is located on the left side, but it can be moved to
the right side and even fixed directly to the wall.
In order to change the source configuration (mounted on the left
side), the following steps must be followed:
1 Loosen and remove the 2 screws at the bottom of the cover,
of the electrical box.
2 Loosen and remove the 2 screws that hold the electrical box
to the indoor unit.
3 Tilt the electrical box forward so that the flanges holding the
electrical hose can be cut.
α
13
PMML0528 rev.1 - 02/2021
α = 15°
4 Carefully separate the electrical box from the indoor unit and
softly pull the electrical hose out of the box.

Mount the electrical box on the right side
a. Loosen and remove the 3 screws holding the lower panel.
b. Remove the bottom panel and leave it somewhere that it
will not be disturbed.
c. Re-route the electrical hose to the inside of the indoor
unit and secure it with the pre-assembled flanges.