Fuses and cable cross-sections according to UL
Supply conditions
Range
Description
Fuses
Cables
Observe all national and regional regulations!
8200 motec
max. current
Type
Mains 1/N/PE AC 230/240 V
E82MV251_2B
E82MV371_2B
Mains 3/PE AC 400/500 V
E82MV551_4B
E82MV751_4B
E82MV152_4B
E82MV222_4B
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
Siemens 5SJ4...-7HG41, Characteristic C
Siemens 5SJ4...-7HG42, Characteristic C
Moeller FAZ-C, Characteristic C
ABB S200U, Characteristic K
ABB S200UP, Characteristic K
Schneider Electric Multi9 C60, Characteristic C
EDK82MV752-BB DE/EN/FR 2.1
Only in accordance with UL 248
System short-circuit current up to 5000 A
System short-circuit current up to 50000 A
permissible
Only in accordance with UL
The cable cross-sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Rated fuse current / cable cross-section
Fuse
L1, L2, L3, N, PE
[A]
[AWG]
10
16
10
16
6
18
6
18
10
16
20
12
20
12
20
12
25
10
35
rms
rms
max. current
[A]
15
15
15
15
15
20
20
20
25
8
35
: All classes are permissible
: Only classes "CC", "J", "T" or "R"
Circuit-breaker
Type



L1, L2, L3, N, PE
[AWG]
14
14
14
14
14
12
12
12
10
8
13