Connection Notes
•
Before opening the lid, ensure there are no dust deposits around the SITRANS LPS200.
Ensure that the atmosphere around SITRANS LPS200 is settled.
•
Use a fuse for the signal output (max. 6 A).
•
Make sure the main voltage does not exceed the maximum voltage listed on the
product label and the setting of the voltage selector.
•
In case of inexpert handling or handling malpractice, the electric safety of the
device cannot be guaranteed.
•
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
Switching Logic (switch-selectable voltage)
LED
red
Switching Logic (non-switch selectable)
Alarm output - Fail-safe option
No
Fault
Fault
LED 2
LED 2
off
red
Page EN-12
Connection example
Full detector with fail-safe option.
Output signal signals a fault if level reaches
high level switching point, the main voltage
fails, there is a faulty connection, or if the
unit is faulty.
SITRANS LPS200 – INSTRUCTION MANUAL
LED
green
signal
output
7ML19985FS62