sigfox ANALOG PWR - Guide utilisateur / User guide version V1.2.0

3.4. Description of the registers

On switching on the product works according to the last saved configuration (Factory Configuration if it is the first start, or if this configuration
has not been changed).
Commands such as Modification TTY<n>=<M> or ATR allow you to change the content of the registers: <n> representing the number of the
register and <m> the value to be assigned. This latter is either a decimal value or a hexadecimal value consistent with the «encoding» column
of the tables below.
Examples:
• ATS300=6 assigns the decimal value 6 in register 300
• ATS302=2 assigns the hexadecimal value 0x02 in register 302
It is imperative to save the parameters with the command AT&W before exiting the Command mode otherwise all changes will be lost.
IMPORTANT: The registers that are not documented (that can appear in the list following the AT/S command) in the paragraphs that follow are
reserved and must not be changed.

3.4.1 Function registers

The list of registers below allows you to change the behaviour of the product application.
Register
Description
300
Transmission period of the Keep Alive frame
301
Transmission period of data sensors
302
Configuration of the channel A sensor
303
Configuration of the event behaviour of channel A
Coding
Details
Decimal
Default: 144
Min/max: 1 to 255:
Units:
X 10min if S306=1
X 10min if S306=2
Decimal
Default: 1
Min/max: 0 to 255:
Units:
X 10min if S306=1
X 10min if S306=2
The value 0 means no periodic sending, therefore event
operation
Hexadecimal Default : 0x00
Bits 0 à 3 : Type
• 0 = none
• 1 = 0-10 V
• 2 = 4-20 mA
Bits 4 to 7: Identifier (free to use)
Hexadecimal Default 0x10
Bits 0 à 1 : Threshold triggering
• 0 = None
• 1 = Low only
• 2 = High only
• 3 = Low and High
Bits 2 to 3: Trigger by digital input
• 0 = Disabled
• 1 = Rising edge
• 2 = Falling edge
• 3 = Rising and falling edges
Bits 4 to 7: Duration of the waiting period
• 0 : Aucune
• 1 : 10 ms
• 2 : 20 ms
• 3 : 50 ms
• 4 : 100 ms
• 5 : 200 ms
• 6 : 500 ms
• 7 : 1 s
EN
• 8 : 2 s
• 9 : 5 s
• A : 10 s
• B : 20 s
• C : 40 s
• D : 60 s
• E : 5 minutes
Page
61
of 73

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8201aa

Table des Matières