The device is equipped with a multi-colour LED with the following meanings:
Standard version
LED
Status
Green Flashes 1:1
Illuminates
Error messages
LED
Status
Red
Illuminates
Illuminates
(approx. 4
seconds)
Illuminates
Flashes 1:1
Yellow Flashes
Illuminates
Illuminates
Function
Switching procedure
Normal mode
Function
Fire/fire detection
Locking element/freely operating door closer switched
off for this period.
(Inspection button or manual triggering button will be
actuated)
External smoke switch connected
Cable break on smoke switch
Short circuit (locking element output), locking ele-
ment inactive.
I
Inspect the system completely for the triggering func-
tion after remedying the short circuit.
Soiling (limiting value nearly reached)
Smoke switch must be exchanged.
I
Locking remains active until the limit value is exceeded
(LED display switches over to RED)
External smoke switch connected
Incorrect configuration of the smoke switch / cable
monitoring
Inspect plug-in bridge J2 (red) / resistors in external
smoke switch
Manual triggering button connected
Cable monitoring
Remove plug-in bridge J1 (black) / inspect resistors in
manual trigger